Leave Your Message
Products Categories
Featured Products

ACR10R-DxxTE Single Phase Solar Inverter Energy Meter

  • Measurement 1-phase Active Power, Reactive Power, Current, Voltage and etc
  • Current Rating up to 300A (paired with external CTs)
  • Communication RS485 (MODBUS-RTU)
  • Application Using in distributed Solar PV and Anti-reflux Inverter
  • Display LCD Dispaly
  • Dimension 54*74*85mm (L*W*H)
  • Installation 35mm DIN Rail
  • Power Supply 85~265V AC or 100~350V DC
  • Certificate CE

General

ACR10R-DxxTE series AC single phase din rail energy meter with split core open ct clamps is suitable for power monitoring of grid-connected PV power station, power demand side management and otherapplications. It is special designed for solar inverters. It can measure electrical parameters including current, voltage, active power, reactive power, apparent power, frequency, power factor and so on. It supports multi-tariff energy metering, 4 quadrant energy metering, harmonic analyse and energy monitoring. Circuit breaker switch 'remote signaling' and 'remote controlling' can be realized with digital input and relay output.

Products Overview

Used for distributed Solar PV

●Reflux Monitoring 

● Harmonic Monitoring

图片2

Bidirectional Metering

● Active Energy Metering

● Reactive Energy Metering

图片3

RS485 Communication

● MODBUS-RTU Protocol

● Communicate with Inverter to realize anti-reflux Function

图片4

Single-phase Two-Wire Connection

● Paired with external split core CT

● Rated Voltage: AC 100V, 400V

图片5

 

LCD Display

● Parameter Display

● Programming Interface

图片6

Keypads HMI for Programming

● Parameter Display Setting

● Communication(address, baud rate and etc.)

 

 图片7

Wiring Instruction

20211115101640_1862220211115101706_51874

Dimension

图片10

Shape and installing size (unit:mm)

图片11

Size of open type transformer (unit:mm)

Application

图片12

Solor PV Power Distribution Monitoring Solution

图片13

ACR10R-DxxT Practical Utility In Distributed Solar PV

Technical Datasheet

Technical parameters

Indicators

Input

Grid

Single-phase

Frequency

45~65Hz

Voltage

Rated voltage: AC 100V, 400V

Overload: 1.2 times the rated voltage(continuous); 2 times the rated voltage lasting for 1 second

Power consumption: less then 0.2VA

Current

Rated current:  10A,20A,40A,80A,120A,200A etc. (for details see product specifications)

Overload: 1.2 times the rated current(continuous);10 times the rated current lasting for 1 second

Power consumption: less then 0.2VA

Output

Communication

RS485 interface, Modbus-RTU

Display

LCD

Measurement precision

Voltage: 0.2 level, current, power Active energy: 0.5 level,0.01Hz frequency, Reactive energy: 1 level

Power supply

AC85~265V or DC100~350V; power consumption ≤10VA

Safety

Power frequency withstand voltage

AC2kV 1 min between power supply // current input//voltage input and communication

AC2kV 1 min between each pair of combinations among power supply, urrent input and voltage input.

Insulating resistor

Input,output terminal to housing >100MΩ

Environment

Working temperature: -10℃~+55℃;storage temperature: -20℃~+70℃

Relative humidity:5%~95%,non-condensing; altitude:≤2500m

Download_file
ACR10R UKCA-EMC Certificate
Download_file
ACR10R power meter V1.6
Download_file
ACR10R series EN 61010 CE-LVD report
Download_file
ACR10R series EN 61326 CE-EMC report
Download_file
ACR10R UKCA-LVD Certificate