ACR10R-DxxTE4 Three Phases Solar Inverter Energy Meter
General
ACR10R-DxxTE4 three pahse din rail energy meter with split core open ct clamps is suitable for power monitoring of grid-connected PV power station, power demand side management and other applications. It is easy to install without removing primary bus bar and cost-effective. It can measure electrical parameters including current, voltage, active power, reactive power, apparent power, frequency, power factor and so on.
It supports multi-tariff energy metering, 4 quadrant energy metering, harmonic analyse and energy monitoring. Circuit breaker switch 'remote signaling' and 'remote controlling' can be realized with digital input and relay output.
Products Overview
Features
|
Used for distributed¢ralized Solar PV ● Rogowski Coil for Centralized Solar PV ● Split-core CTs for Distributed Solar PV ● Reflux Monitoring ● Harmonic Monitoring |
|
|
Bidirectional Metering ● Active Energy Metering ● Reactive Energy Metering |
|
|
RS485 Communication ● MODBUS-RTU Protocol ● Communicate with Inverter to realize anti-reflux Function |
|
|
Paired with external CTs or Rogowski Coil ● Rated Current of CTs: up to 300A ● Rated Current of Rogowski Coil: up to 20000A |
|
|
LCD Display ● Parameter Display ● Programming Interface |
|
|
Keypads HMI for Programming ● Parameter Display Setting ● Communication(address, baud rate and etc.) ● Wiring: 3P3W,3P4W |
|
Wiring Instruction

Dimension

Shape and installing size (unit:mm)

Size of open type transformer (unit:mm)
Application

Solor PV Power Distribution Monitoring Solution

ACR10R-DxxTEx Practical Utility In Distributed Solar PV
Technical Datasheet
|
Technical parameter |
Value |
||||
|
Input |
Net work |
3-phase 3-wire,3-phase 4 wire |
|||
|
Frequency |
45~65Hz |
||||
|
Voltage |
Rating:AC 57.7V/100V(100V)、220V/380V(400V) |
||||
|
Overload:1.2-fold rating(continuous);2-fold rating/1second |
|||||
|
Consumption:<0.2VA |
|||||
|
Current |
Rating: 80A,120A,200A .etc(See specific product specifications,special parameters can be customized) |
||||
|
Overload:1.2-fold rating(continuous);10-fold rating/1 second |
|||||
|
Consumption:< 0.2VA |
|||||
|
Output
|
Electric energy |
Output mode:Open-collector photocoupler pulse,two way output |
|||
|
Three-phase |
Pulse constant:4000、8000imp/kWh |
||||
|
Communication |
RS485 interface,Modbus-RTU Protocol |
||||
|
Display mode |
LCD |
||||
|
Function |
Switching |
input |
Four way dry contact input |
||
|
output |
Output mode: two way relay nO contact output |
||||
|
Contact capacity:AC 250V/3A、DC 30V/3A |
|||||
|
Measuring accuracy |
Frequency0.05Hz、reactive electric energy1class、other 0.5class |
||||
|
Power supply
|
AC85~265V or DC100~350V;DC24V(±10%);DC48V(±10%) Consumption≤10VA |
||||
|
Safety |
Power-frequency withstand voltage |
Power frequency withstand voltage between Auxiliary power and switch volume output and current input and voltage input and communication and pulse output and switch volume input terminal is AC2kV 1min; Power frequency withstand voltage between auxiliary power and switch volume output and current input voltage input terminal is AC 2kV/1min; Power frequency withstand voltage between communication and pulse output and switch volume input terminal is AC 1kV/1min; |
|||
|
Insulation resistance |
Input,Output terminal to housing>100MΩ |
||||
|
Environment |