ADL200N-CT Single-phase CT Energy Meter
Overview
Main Features
|
Bidirection Metering ● For grids import and solar export metering ● For ESS charge&discharge metering ● Forward&backward metering |
|
|
Paired with Inverter for Zero Export ● 1-channel RS485 to communicate with inveter ● 100ms fast response time (voltage, current, power) ● Bidirectional metering |
|
|
Diverse Electricity Parameters Measurement ● U (Voltage) ● I (Current) ● P (Power) ● Q (Reactive power) ● S (Apparent power) ● PF (Power factor) ● kWh (Kilowatt-hours) ● kVarh (Kilovar-hours) |
|
Dimension&Packagement
DIN Rail Installation
Application in IoT System
Electric performance
|
Input voltage |
Reference voltage |
110~240Vac |
|
Reference frequency |
45~65Hz |
|
|
Power consumption |
<10VA, <2W |
|
|
Input current |
Input current |
Optional 80A, 120A, 200A, 300A AC (via paired CT) |
|
Overload |
1.2 times of rating [continuous] |
|
|
Consumption |
<0.2VA |
|
|
Measurement performance |
Accuracy of measuring |
Class 1.0 [Active energy] |
|
Active pulse |
Pulse width |
80±20ms |
|
Pulse constant |
1000imp/kWh |
|
|
Communication |
Interface |
RS485(A+、B-) |
|
Connection mode Connection mode |
Shielded twisted pair conductors |
|
|
Protocol |
MODBUS-RTU |
Work environment
|
Temperature range |
Work temperature |
-40℃~70℃ |
|
Storage Temperature |
-40℃~70℃ |
|
|
Relative humidity |
≤95%(No condensation) |
|
|
Altitude |
<2000m |
|
|
Working Environment |
Indoor environment |
|