ADW300 Three Phase IoT wireless Power Meter
General
ADW300 wireless meter is mainly used to measure three-phase active power in low-voltage network. It has the functions of RS485 communication and 470MHZ wireless communication. It is convenient for users to monitor, collect and manage electricity. It can be flexibly installed in the distribution box to realize the measurement, statistics and analysis of individual electric energy in different regions and loads.
Main Functions
Accuracy
Active power: Class 0.5S
Reactive power: Class 2
Pulse Output
Constant: 6400imp/kWh;
Consumption
<10VA(Single phase)
Dimension (L*W*H)
Panel size (L×W):82*87.8*71.5 mm
Wireless
Transmission on 470MHz and maximum distance
in open space is 1km; 2G; NB
Frequency
Range:50~60Hz
Starting current
2‰ln
Panel Overview

① DO / DI
② Brand
③ Model Number
④ Antenna Terminal
⑤ Pulse Output Light
⑥ Infrared Status
⑦ Auxiliary Power Supply
⑧ Temperature / Leakage Current
Connection

3 Phase 3 Wire 3 Phase 4 Wire 3 Phase 4 Wire with External CT
Solutions
Dimention
Package
|
kaging Overview (Minimum) |
|
|
|
Packing Dimension and Weight (Minimum) |
Minimum Package Contain 1 pcs Product Dimension: 170mm*150mm*130mm
|
Total G.W. (1 pcs) 0.233 KG |
|
Packing Dimension and Weight (Large) |
Large Package Contain 36 pcs Products Dimension: 540mm*530mm*490mm
|
Total G.W. (48 pcs) 10 KG |
|
Average Lead Time |
Manufacturing: 3~4 days (If paired with system need extra 1~2 days for adjustment)
|
Shippment: 8~9 days (World Wide Shipment) |
|
Product HS Code |
9028301400
|
|
|
CO Country of Origin |
China
|
|
Technical Datasheet
|
Parameter |
Description&Value |
|
|
Voltage Input |
Rated Voltage |
3x380~456Vac L-L or 3x660~792Vac L-L (via direct connection) 3x100~120Vac L-L (via PTs) |
|
Reference Frequency |
45~65Hz |
|
|
Power Consumption |
<0.5VA (each Phase) |
|
|
Current Input |
Rated Current |
3x1(6)A AC (via CTs) |
|
Starting Current |
1% Ib (Class 0.5); 4% Ib(Class 1) |
|
|
Power Consumption |
<1VA (each Phase) |
|
|
Phase Wiring |
3P4W |
3-phase 4-wire |
|
3P3W |
3-phase 3-wire |
|
|
Auxiliary Power Supply |
Voltage Range |
85~265Vac |
|
Power Consumption |
<2W |
|
|
Measurement Performance |
Standard |
IEC 62053-22:2003; IEC 62053-21:2003 |
|
kWh Accuracy |
Class 0.5S |
|
|
Pulse |
Width of Pulse |
80±20ms |
|
Pulse Constant |
6400imp/kWh; 400imp/kWh |
|