AID150 Alarm&Display Device

  • Installation panel
  • Voltage DC24V
  • Consumption <0.6W
  • Number of monitored systems 1
  • Alarm method sound-light alarm
  • Alarm type insulation failure, overload, overheat, equipment failure
  • Display led display
  • Communication RS485, MODBUS-RTU

Features

Remote Monitoring

(Duplicate data of AIM Series Insulation monitor) 

● Insulation Fault

● Alarm

● Operating Message

● Through RS485 (MODBUS-RTU)

 图片2

LED Indicator

● On-off status of devices

● Insulation Fault

● Overload

● Over-temperature

 图片3

HMI Interface for remote Parameter Setting&Alarm Mute

● Set Response Time of Insulation Monitoring

● Mute Audible Alarm

 图片4

Display Sample

图片5

Wiring

图片6

Typical Connection

图片7

Technical Datasheet

Parameters/Model

AID10

AID120

AID150

Auxiliary power

Voltage 

DC 24V 

Power consumption

< 0.6W 

Insulation resistance measurement range 

— 

0—999kΩ 

— 

Insulation alarm value range 

 

50—999kΩ 

 

Transformer load rate display 

— 

Percentage display 

— 

Load current alarm settings

14A、18A、22A、28A、35A、45A

Temperature alarm value range 

0~+200℃ 

Alarm 

Audible and visible alarm 

Alarm Type 

Insulation fault, overload, over-temperature, equipment failure 

Communication 

RS485 interface, MODBUS-RTU protocol 

Display method 

— 

LED Display

128*32 LCD 

Download_file
AID150 MANUAL