AMC16-DETT Base Station DC Energy Meter for 5G Tower
General
AMC16-DETT Base Station DC Energy Meter for 5G Tower is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering. The meter could measure 6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software. It has the functions of telemetering, teleindication, teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction.
Products Overview
Features
|
Multi-circuit Metering ● Up to 6-circuit DC circuit monitoring ● Rated Voltage [DC]: -48Vdc ● Rated Current [DC]: 5Vdc [via hall sensor] ● 1 extra Utility Voltage Monitoring [via -/5Vdc transducer] |
|
|
Wired Communications ● 1-way RS485 Interface ● MODBUS-RTU Protocol ● Baud Rate: 9600 default [optional 1200, 2400, 4800] ● Wiring Cable Recommend: RVSP 2x1.5²mm |
|
|
Extra Power Output ● Applicatrion: ±12Vdc Power Output for 6 paired Hall Sensors ● Output Specs: +12V/100mA, -12V/50mA |
|
Dimension
Wiring Instruction
Structure
Technical Datasheet
|
Technical parameter |
Index |
|
|
input |
DC rated voltage |
1 channel: -48VDC |
|
DC current |
6 channels hall sensors output is 5V,current ratio can be set according to the actual ratio |
|
|
Commercial power monitoring |
1 channel transmitter input: 0-5VDC or 4-20mA |
|
|
Overload capacity |
Voltage:1.2times continued,2 times continued 1s; Current: 1.2 times continued,10 times continued 1s. |
|
|
Accuracy (superposition hall sensors) |
1%In≤I≤10%In accuracy ±2.5%; I>10%In accuracy ±2% |
|
|
Measurement resolution |
Voltage output accuracy 0.01V; current output accuracy 0.01A; power output accuracy 0.01kw; energy output accuracy 0.01kWh. |
|
|
functions |
Basic function |
Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication. |
|
Metering function |
Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts. Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change. |
|
|
Alarm function |
DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm,memory failure alarm, AC input power failure alarm |
|
|
Timing function |
support broadcast timing, could remote timing to the meter through RS485 communication. |
|
|
Communication |
Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or custmized |
|