AMC200L-4/8E3 AC Multi Channel Energy Meter

  • Funtion Full power parameter measurement ,Active 2DI + Passive 4DI + 2DO,4 NTC Temperature,1 T&H
  • Circuit 4 or 8 Channels 3 phase or 12 or 24 channels single phase mA class current sensor
  • Communication RS485,Modbus RTU protocol
  • Applicaiton Telecom Base station,other multi channels applicaiton

General

AMC200(L) AC multi-loop intelligent power acquisition and monitoring device is mainly used for the measurement of full electrical parameters of multiple loops, and can access the current input of up to 8 three-phase loops or 24 single-phase loops at the same time. Can measure voltage and current, power, power factor and other parameters.

Function

1) Maximum 8 three-phase or 24 single-phase circuit full electric parameter measurement, current transformer external;

2) Monitor the phase voltage/current, zero sequence current, frequency;

3) Monitor the phase power, total power (active power, reactive power, apparent);

4) Monitoring each phase power factor, total power factor, four-quadrant power statistics;

5) The use of simplified Chinese characters LCD display, English Version also. with historical power data and historical alarm information storage function:

a. By default, historical data is saved once a day at 0 o 'clock. Each channel and each item of data (total active power, total active power, and three-phase current) can be stored 1000 times.

b. The interval for storing historical data onsite is 15 minutes. Each channel and each item of data (total active energy, total active power, three-phase current) can be stored 5000 times.

c. 24 pieces of historical electricity data are stored on the monthly meter reading day.

d. Historical alarms are stored in real-time mode. A maximum of 500 historical alarms can be stored.

6) Support over voltage, over current, phase break, DI linkage alarm output;

7) Four passive switching input, two active switching input, two switching output;

8) Standard RS485 communication, optional Modbus-RTU protocol or YD/T 1363 protocol;

9) One loop temperature and humidity measurement, 4 loops  NTC measurement;

Dimension

20250613083914_77752

Wiring Instruction

20250613084239_37325

Structure

20250613084522_16954

Technical Datasheet

Technical Parameter

Technical Indicator

Input

Frequency

45~65Hz;

Voltage

Rating: AC 3×220V/380V;

Overload: 1.2 times rated (continuous); 2 times rating value/1 second;

Power consumption: ≤0.5VA (per channel);

Current

Rating: AC xxxA/50mA, need external transformer;

Overload: 1.2 times rated (continuous); 10 times rating value /1 second;

Power consumption: ≤0.5VA (per channel);

Function

 

Pulse Output

Output mode: open collector optocoupler pulse (default 400imp/kWh);

Communication

Modbus-RTU or YD/T 1363 protocol(use in China);Baud rate 1200~38400;

Switch

Input

Output

Output mode: relay normally open contact output;

Contact capacity: AC 250V/3A or DC 30V/3A;    

NTC Temperature Measurement

Temperature: -20~100℃ (accuracy ±2℃);

Temp&Humidity

Measurement

Temperature: -20~100℃ (accuracy ±2℃); Humidity: 20-90%RH (accuracy ±5%RH)

Measurement accuracy

Frequency 0.05Hz, voltage and current 0.5 level, active power 1 level;

Auxiliary power supply

AC/DC 85 ~ 265V; Power consumption ≤10VA;

Security

Power Frequency Withstand Voltage

>AC 2kV/1min;  

Insulation Resistance

Input and output end to the housing>100MΩ;

Environment

Operating temperature: -20℃ ~ +60℃;

Storage temperature: -40℃ ~ +70℃;

Relative humidity: ≤95% no condensation;

Altitude: ≤2500m;

Electromagnetic compatibility

Surge (impact) immunity test level 4

Electrostatic discharge immunity test level 3

Electrical fast transient pulse group immunity test level 3

Download_file
AMC200(L) Installation Instructions