DJSF1352-RN-6 Din Rail DC Energy Meter
General
DJSF1352-RN-6 rail-mounted DC energy meter is designed mainly for DC charging piles, telecommunication base stations, solar photovoltaic and other application occasions. This series of instruments can measure voltage, current, power and positive and negative energy in the DC system. The test results can be used for local display and can also be connected with industrial control equipment and computers to form a measurement and control system.
Products Overview
Features
|
Accuracy Pulse output Communication |
|
|
Power Supply: AC/DC 85-265V or DC12V-48V Dimension(L*W*H): 108*70*94 mm Temperature: Normal operating temperature:-25℃~+65℃ Storage temperature:-40℃~ |
|
Dimension & Installation

Shape and installation dimensions

Terminals and wiring

Shunt input and Hall sensor input
Technical Datasheet
|
Technical Parameters |
Index |
|||
|
Input |
Nominal value |
Voltage input range |
Current input |
|
|
DC 0-100V、DC 0-1500V See the physical wiring diagram |
Shunt: 0-75mV Hall sensor: 0-5V, 0-200mA
|
|||
|
Overload |
1.2 times can sustain normal operation, 2 times can sustain 1 second |
|||
|
Power consumption |
Voltage: ≤0.2VA, current ≤0.1VA |
|||
|
Accuracy class |
Class 0.5 |
|||
|
Function |
Display |
8-bit segment LCD screen (LCD) |
||
|
Communication Interface |
RS485(two options) |
|||
|
Communication protocol |
Modbus-RTU,DL/T 645-2007,DLT698
|
|||
|
Switch |
Switch output (DO) |
2 relay outputs, 2A/30VDC or 2A/250VAC |
||
|
Switch input (DI) |
2 dry contact inputs |
|||
|
Analog |
Analog output (AO) |
4-20mA output (0.5 level) |
||
|
Pulse output |
Two-way power pulse output (the second power pulse can be switched to second pulse) |
|||
|
See the display in SYS->PULS in the meter menu setting, for example: display 100, which means 100imp/ kWH |
||||
|
Working power supply |
Voltage |
AC/DC 85-265V or DC 12V-48V |
||
|
Power consumption |
≤ 10W |
|||
|
Power frequency withstand voltage |
Power supply//signal input//RS485 communication 4kV/1min; Except for power supply, signal input and RS485 communication, other unconnected circuits are 2kV/1min |
|||
|
Insulation resistance
|
≥ 100M Ω |
|||
|
Average barrier-free working time |
≥50000h |
|||
|
Environment |
Temperature |
Working temperature: -25℃~+65℃ Storage temperature: -40℃~+80℃ |
||
|
Humidity |
≤95%RH, no condensation, no corrosive gas |
|||
|
Altitude |
≤3000m |
|||